Enhancement of power efficiency of evaporating-condensing heat exchangers


  • A.N. Gershuni National Technical University of Ukraine "Igor Sikorsky Kyiv Polytechnic Institute"
  • Ye.N. Pysmennyy National Technical University of Ukraine "Igor Sikorsky Kyiv Polytechnic Institute"
  • A.P. Nishchik National Technical University of Ukraine "Igor Sikorsky Kyiv Polytechnic Institute"
Keywords: evaporating-condensing heat exchanger, optimal ratio between the lengths of zones of heat transferring elements, minimal power for pumping heat exchanging media

Abstract

The aspects of heat transfer in evaporating-condensing heat exchangers conditioning their thermophysical merits and advantages as regards routine heat transferring devices are determined and analyzed. It is shown that implementation of one of these aspects which is transformation of heat flux density in its transferring from “hot” medium to “cold” one by changing the ratio of the lengths of the evaporation and condensation zones of evaporating-condensing heat transferring elements (positioning of tube plate separating the channels with heat exchanging media) allows studying optimization of the said ratio in respect to getting the minimal thermal and aerodynamic resistances of evaporating-condensing heat exchangers.

Thus, the concerned work on one of the parts of such study is aimed to derive the correlations for optimal ratio of evaporation and condensation zones in gas-to-gas heat exchangers based on vertical transversely finned tubular thermosiphons to spend the minimal power required to pump heat-exchanging media under the specified conditions of heat transfer.

As an objective function of optimization the dimensionless ratio of transferred heat flux to the sum of the powers provided to pump the heat-exchanging media through the heat-exchanger channels is accepted. This ratio is called a factor of heat exchanger power efficiency.

In the concerned study the functional dependence of dimensionless power efficiency factor of evaporating-condensing heat exchanger upon dimensionless ratio of the lengths of evaporation and condensation zones is derived. The performed extremum research of the dependence revealed that it has an extremum for an actual range of the determining parameters and this extremum is the maximum. The study resulted in an equation of optimal relationship between the zone lengths (the heights of the channels occupied by flowing heat-exchanging media) that corresponds to the maximal factor of power efficiency.

References

1. Zohuri B. Heat Pipe Design and Technology. Second Edition, Switzerland, Springer, 2016, 513 p.
2. Semena M.G., Gershuni A.N., Zaripov V.K. [Heat pipes with metal fiber capillary structures], Kyiv, [High school], 1984, 216 p. (in Rus.)
3. Bezrodnyy M.K., Pioro I.L., Kostiuk T.O. [Processes of transfer in two-phase thermosyphon systems. Theory and practice], Kyiv, [Fact], 2005, 704 p. (in Rus.)
4. Gershuni A.N., Nishchik A.P. [A comparative analysis of heat transfer capabilities of evaporation-condensation type heat exchangers and recuperative tube-type heat exchangers], [Industrial Heat Engineering], 2010, V.32, No.3, P.28-36. (in Ukr.)
5. Gershuni A.N., Pysmennyy Ye.N., Nishchik A.P. [Optimization of evaporation-and-condensation heat-exchanger performance], [Thermophysics and Thermal Power Engineering], 2019, V.41, No.2, P.41-47. (Ukr.)
6. Pysmennyy Ye.N. [Heat exchange and aerodynamics in the package of transversely finned tubes], Kyiv, [Alterpres], 2004, 244 p. (in Rus.)
7. Pysmennyy Ye.N. [Estimation of convective transversely finned heating surfaces], Kyiv, [Alterpres], 2003, 184 p. (in Rus.)

Abstract views: 76
PDF Downloads: 34
Published
2020-04-12
How to Cite
Gershuni, A., Pysmennyy, Y., & Nishchik, A. (2020). Enhancement of power efficiency of evaporating-condensing heat exchangers. Thermophysics and Thermal Power Engineering, 42(1), 35-41. https://doi.org/https://doi.org/10.31472/ttpe.1.2020.4
Section
District and Industrial Heat Power, Renewable Energy Systems, Energy Efficiency